Parameter assignment / addressing
3.4 Configuring PROFINET (only for D410 PN)
SIMOTION D410
62
Commissioning Manual, 02/2012
Changing the IP address, device name, network gateway
Set the IP address, the subnet mask and, if necessary, the data for a gateway (router
address) in order to enable communication over PROFINET with SIMOTION D410.
If you want to change the properties in the PROFINET subnet, you can change them using
the "Reachable nodes" function in SIMOTION SCOUT or in the HW Config.
The "Reachable nodes" function in SIMOTION SCOUT is described in the section titled
"Initializing SIMOTION D410".
To configure and transfer the properties in HW Config, proceed as follows:
1.
Open your project in SIMOTION SCOUT.
2.
Open HW Config. Double-click the PROFINET interface to open the "Properties" dialog
box.
3.
Click "Properties". The "Properties - Ethernet Interface" dialog box opens.
4.
Click "New". The "New Subnet Industrial Ethernet" dialog box opens. Rename the new
subnet, or accept the default name by clicking "OK".
5.
Select the new Ethernet subnet which is now displayed in the "Properties - Ethernet
Interface" dialog box.
6.
Enter the required addresses in the "IP address" and "Subnet mask" fields of the
"Properties - Ethernet interface" dialog. In the "Gateway" field, select whether or not you
wish to use a router and, if you do, enter the router address. Confirm with "OK".
7.
Close the "Properties" dialog by clicking "OK".
8.
Save and compile the modified hardware configuration.
9.
Download the new hardware configuration on PROFINET to your SIMOTION D410.