Installation
4-62
E
Siemens AG, 2003 All rights reserved
SIMOTION C230-2, 04.2003 Edition
4.1.5
Layout of modules on several racks
Overview
With the C230-2, a 2-tier layout is possible.
Interconnection modules
Interconnection modules are required for the 2-tier layout which route the back-
plane bus from one rack to the other. The C230-2 is always on rack 0.
Interconnection module
Usable for ...
Order number
IM 365 SEND
Rack 0
6ES7 365-0BA01-0AA0
IM 365 RECEIVE
Rack 1
IM 365 interconnection modules
The two IM 365 interconnection modules have a fixed connection via a 1 m long
connection cable.
The total power consumption of the inserted I/O modules of both racks must not
exceed 1.2 A; the power consumption from rack 1 is limited to 800 mA.
Rules
The following rules apply with respect to the layout of the modules on two racks:
S
The interconnection module always occupies Slot 3 and is always left of the first
signal module.
S
No more than 8 modules may be inserted per rack. These modules are always
to the right of the interconnection modules.
S
The number of inserted modules is limited by the permissible power consump-
tion from the backplane bus. The total current drawn must not exceed 1.2 A
(see “Technical data” table of the individual modules in the manual S7-300 Au-
tomation Systems, M7-300 module data).
Содержание SIMOTION C230-2
Страница 10: ...Table of Contents Contents 10 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Страница 16: ...Product Overview 1 16 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Страница 70: ...Installation 4 70 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Страница 124: ...Commissioning 8 124 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Страница 130: ...Maintenance 9 130 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Страница 141: ...B 141 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition EC Declaration of Conformity B ...
Страница 144: ...EC Declaration of Conformity B 144 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...