Installation
4-61
E
Siemens AG, 2003 All rights reserved
SIMOTION C230-2, 04.2003 Edition
4.1.4
Layout of modules on a rack
Rules
The following rules apply with respect to the layout of the modules on a rack:
S
No more than 8 modules may be inserted to the right of the C230-2.
S
The number of insertable modules is also limited by their power consumption
from the backplane bus (see “Technical data” table of the individual modules in
the manual S7-300 Automation Systems, M7-300 module data).
The total power consumption from the backplane bus of all modules that are
mounted on a rack must not exceed 1.2 A.
Fig. 4-3 shows the order of the modules in an installation with 8 I/O modules.
PS
C230-2
I/O modules
Fig. 4-3
Layout of modules on a rack