Networking
7-105
E
Siemens AG, 2003 All rights reserved
SIMOTION C230-2, 04.2003 Edition
7.1.3
Cable lengths
Segment in subnet
The cable length in a segment of a subnet depends on the baud rate (see
Table 7-1).
Table 7-1
Permissible cable length of a segment in the subnet as a function of the baud
rate
Baud rate
Max. cable length of a segment (in m)
9.6 to 187.5 bits/s
1000
1)
500 Kbits/s
400
1.5 Mbits/s
200
3 to 12 Mbits/s
100
1) For isolated interface
Longer cable lengths
If you have to use longer cable lengths in a segment than are permissible, you
must use RS 485 repeaters. The maximum possible cable lengths between two
RS 485 repeaters correspond to the line length of a segment (see Table 7-1). How-
ever, please note that with these maximum cable lengths, no further node is per-
missible between the two RS 485 repeaters. You can fit up to nine RS 485 repeat-
ers in sequence.
Please note that an RS 485 repeater must be counted as a node in the overall
number of nodes that can be connected in the subnet, even if this does not have
its own PROFIBUS address.
Содержание SIMOTION C230-2
Страница 10: ...Table of Contents Contents 10 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Страница 16: ...Product Overview 1 16 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Страница 70: ...Installation 4 70 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Страница 124: ...Commissioning 8 124 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Страница 130: ...Maintenance 9 130 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Страница 141: ...B 141 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition EC Declaration of Conformity B ...
Страница 144: ...EC Declaration of Conformity B 144 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...