9.1.2
First inspection
Perform the following checks after approximately 500 operating hours or one year, whichever
comes first:
Table 9-1
Checks after installation or repair
Check
When the
motor is
running
At stand‐
still
The electrical parameters are maintained.
X
The permissible bearing temperatures are not exceeded.
X
The smooth running characteristics and machine running noise have not
deteriorated.
X
The motor foundation has no cracks and indentations. (*)
X
X
(*) You can perform these checks while the motor is at standstill or, if required, while running.
Further checks
Further checks may be required if so specified in supplementary instructions or in accordance
with the plant-specific conditions.
NOTICE
If you detect any deviations during the inspection, you must rectify them immediately. They
may otherwise damage the motor.
9.1.3
General inspection
Check that the installation conditions are observed. We recommend that the following checks
are performed after approx. 16 000 operating hours or at the latest after two years:
Table 9-2
Checks that have to be performed during the general inspection
Checking
When the
motor is
running
At stand‐
still
The electrical parameters are maintained
X
The permissible bearing temperatures are not exceeded
X
The smooth running characteristics and machine running noise have not
deteriorated
X
The motor foundation has no cracks and indentations (*)
X
X
The machine is aligned within the permissible tolerance ranges
X
All the fixing bolts/screws for the mechanical and electrical connections have
been securely tightened
X
All the potential connections, grounding connections and shield supports are
correctly seated and properly bonded
X
The winding insulation resistances are sufficiently high
X
Maintenance
9.1 Inspection and maintenance
SIMOTICS XP 1MD4/1MD5
78
Operating Instructions 05/2015
Содержание SIMOTICS XP 1MD4
Страница 2: ...13 07 2015 11 26 V8 00 ...
Страница 10: ...Table of contents SIMOTICS XP 1MD4 1MD5 10 Operating Instructions 05 2015 ...
Страница 12: ...Introduction SIMOTICS XP 1MD4 1MD5 12 Operating Instructions 05 2015 ...
Страница 20: ...Safety notes 2 11 Ventilation SIMOTICS XP 1MD4 1MD5 20 Operating Instructions 05 2015 ...
Страница 26: ...Description SIMOTICS XP 1MD4 1MD5 26 Operating Instructions 05 2015 ...
Страница 40: ...Preparations for use 4 10 Converter operation SIMOTICS XP 1MD4 1MD5 40 Operating Instructions 05 2015 ...
Страница 50: ...Assembling 5 3 Installing the machine SIMOTICS XP 1MD4 1MD5 50 Operating Instructions 05 2015 ...
Страница 74: ...Operation 8 7 Faults SIMOTICS XP 1MD4 1MD5 74 Operating Instructions 05 2015 ...
Страница 90: ...Maintenance 9 2 Repair SIMOTICS XP 1MD4 1MD5 90 Operating Instructions 05 2015 ...
Страница 110: ...Disposal 11 4 Disposal of components SIMOTICS XP 1MD4 1MD5 110 Operating Instructions 05 2015 ...
Страница 126: ...Index SIMOTICS XP 1MD4 1MD5 126 Operating Instructions 05 2015 ...
Страница 127: ...AE EC Declaration of Conformity U161 AD EC Declaration of Conformity U163 AA R No 20000h U165 ...
Страница 128: ...Siemens AG Process Industries and Drives Postfach 48 48 90026 NÜRNBERG GERMANY www siemens com drives ...