CAUTION
Working on terminal boxes of the "Ex e" type of protection with undrilled cable entry plate
This can result in death, serious injury or material damage.
Ensure that the cable entry plate is still strong enough after drilling the threads.
6.2.3
Connecting the grounding conductor
The cross-section of the machine grounding conductor must comply with the installation
regulations and also with IEC / EN 60204-1.
Table 6-1
Determining the cross-section of the grounding conductor
External cable cross-section S
Cross-section of the grounding conductor [mm²]
S ≤ 16 mm²
S
16 mm² < S ≤ 35 mm²
16 mm²
S > 35 mm²
S/2
A terminal strip for grounding is fitted either on the stator casing or on the flanged endshield,
depending on the frame size. The grounding point is marked.
The terminal strip is suitable for connecting stranded cables with cable lugs or connecting flat
straps. In addition, all motors have a PE terminal within the terminal box.
When connecting up the grounding conductor, ensure that the contact surface of the
connection is bare and protected against corrosion using a suitable agent, e.g. with acid-free
Vaseline.
6.2.4
Circuit diagram in the terminal box cover
Data on the connection and connecting the motor winding can be found in the circuit diagram
in the cover of the terminal box.
6.2.5
Terminal designation
According to IEC / EN 60034‑8, the following basic definitions apply to the terminal
designations for 3-phase machines:
Table 6-2
Terminal designations using the 1U1-1 as an example
1 U 1 - 1 Designation
x
Index for pole assignment for pole-changing machines where applicable. A lower
index signifies a lower speed. Special case for split winding.
x
Phase designation U, V, W
Electrical connection
6.2 Connecting
SIMOTICS XP 1MD4/1MD5
Operating Instructions 05/2015
53
Содержание SIMOTICS XP 1MD4
Страница 2: ...13 07 2015 11 26 V8 00 ...
Страница 10: ...Table of contents SIMOTICS XP 1MD4 1MD5 10 Operating Instructions 05 2015 ...
Страница 12: ...Introduction SIMOTICS XP 1MD4 1MD5 12 Operating Instructions 05 2015 ...
Страница 20: ...Safety notes 2 11 Ventilation SIMOTICS XP 1MD4 1MD5 20 Operating Instructions 05 2015 ...
Страница 26: ...Description SIMOTICS XP 1MD4 1MD5 26 Operating Instructions 05 2015 ...
Страница 40: ...Preparations for use 4 10 Converter operation SIMOTICS XP 1MD4 1MD5 40 Operating Instructions 05 2015 ...
Страница 50: ...Assembling 5 3 Installing the machine SIMOTICS XP 1MD4 1MD5 50 Operating Instructions 05 2015 ...
Страница 74: ...Operation 8 7 Faults SIMOTICS XP 1MD4 1MD5 74 Operating Instructions 05 2015 ...
Страница 90: ...Maintenance 9 2 Repair SIMOTICS XP 1MD4 1MD5 90 Operating Instructions 05 2015 ...
Страница 110: ...Disposal 11 4 Disposal of components SIMOTICS XP 1MD4 1MD5 110 Operating Instructions 05 2015 ...
Страница 126: ...Index SIMOTICS XP 1MD4 1MD5 126 Operating Instructions 05 2015 ...
Страница 127: ...AE EC Declaration of Conformity U161 AD EC Declaration of Conformity U163 AA R No 20000h U165 ...
Страница 128: ...Siemens AG Process Industries and Drives Postfach 48 48 90026 NÜRNBERG GERMANY www siemens com drives ...