Connecting
6.2 Electrical connection
1FE1 synchronous built-in motors
108
Hardware Installation Manual, 12/2016, 610.43000.40b
6.2.7
Connecting to a converter
To connect the motor to a converter, use MOTION-CONNECT cables or shielded connecting
cables.
The braided shielding must have good electrical conductivity. Prefer braided shielding made
of copper or aluminum.
The shield must be connected at both ends to the motor and the converter; unshielded cable
ends must be kept as short as possible.
Attach the shielding with a large area as 360° contact to the converter and to the motor. Use
for instance, EMC glands at the cable entries.
6.2.8
Connection overview
The circuit diagram contains information about wiring and connecting the motor winding.
1
Ground connection
2
Temperature sensor (1 x reserve)
3
Encoders
4
VP module (if required)
Figure 6-2
Circuit diagram with SIMODRIVE (example)
Содержание Simotics M-1FE1 Series
Страница 1: ......
Страница 2: ......
Страница 8: ...Introduction 1FE1 synchronous built in motors 8 Hardware Installation Manual 12 2016 610 43000 40b ...
Страница 12: ...Table of contents 1FE1 synchronous built in motors 12 Hardware Installation Manual 12 2016 610 43000 40b ...
Страница 40: ......
Страница 50: ......
Страница 136: ...Operation 8 4 Stoppages 1FE1 synchronous built in motors 136 Hardware Installation Manual 12 2016 610 43000 40b ...
Страница 138: ...Service and maintenance 1FE1 synchronous built in motors 138 Hardware Installation Manual 12 2016 610 43000 40b ...
Страница 144: ...1FE1 synchronous built in motors 144 Hardware Installation Manual 12 2016 610 43000 40b ...
Страница 146: ...List of abbreviations 1FE1 synchronous built in motors 146 Hardware Installation Manual 12 2016 610 43000 40b ...
Страница 149: ......
Страница 150: ......