7.8
Set values for temperature monitoring of the bearing thermometer
Before the first machine run, set the tripping temperatures of the monitoring system.
Table 7-1
Guidelines for setting the tripping temperature of bearing thermometers
Set value
Temperature
Prior to commissioning
For shutdown
T
0
= 110 °C
During operation
For warning
T
1
= T + 5 K (max. 115 °C)
For shutdown
T
2
= T + 10 K (max. 120 °C)
T = temperature in steady state (°C)
7.9
Setting values for temperature monitoring (slot thermometer)
Before the first machine run, set the tripping temperatures of the monitoring system.
The tripping temperatures of winding thermometers differ depending on the temperature class
of the machine. The temperature class can be found on the rating plate.
Table 7-2
Guidelines for setting the tripping temperature of winding thermometers
Set value
Temperature class F/B
Temperature class F/F
Prior to commis‐
sioning
for shutdown
T0 = 120°C
T0 = 140°C
During operation
for warning
T1 = T + 10 K (max. 135°C)
T1 = T + 10 K (max. 150℃)
for shutdown
T2 = T + 15 K (max. 140°C)
T2 = T + 15 K (max. 155℃)
T = temperature in steady state (°C)
7.10
Switching off the machine
● Do not switch off the water-cooling system immediately after switching off the machine.
Wait for the machine to cool. This will prevent the accumulation of residual heat.
7.11
Avoidance of condensation or formation of condensation within the
machine
● If the controller does not do this automatically, switch on any anti-condensation heating
during stoppages. This will avoid the formation of condensation.
● Observe the specifications on the anti-condensation heating plate in this regard.
Start-up
7.8 Set values for temperature monitoring of the bearing thermometer
SIMOTICS HT Series HT-direct 1FW4...1......A
Operating Instructions 11/2018
85
Содержание SIMOTICS HT Series
Страница 2: ...13 11 2018 16 25 V5 00 ...
Страница 10: ...Table of contents SIMOTICS HT Series HT direct 1FW4 1 A 10 Operating Instructions 11 2018 ...
Страница 26: ...Description SIMOTICS HT Series HT direct 1FW4 1 A 26 Operating Instructions 11 2018 ...
Страница 62: ...Assembly 5 6 Insulated bearings SIMOTICS HT Series HT direct 1FW4 1 A 62 Operating Instructions 11 2018 ...
Страница 108: ...Maintenance 9 2 Corrective Maintenance SIMOTICS HT Series HT direct 1FW4 1 A 108 Operating Instructions 11 2018 ...
Страница 116: ...Disposal 11 7 Disposal of components SIMOTICS HT Series HT direct 1FW4 1 A 116 Operating Instructions 11 2018 ...
Страница 118: ...Service and Support SIMOTICS HT Series HT direct 1FW4 1 A 118 Operating Instructions 11 2018 ...
Страница 122: ...Quality documents SIMOTICS HT Series HT direct 1FW4 1 A 122 Operating Instructions 11 2018 ...
Страница 127: ......