The following information is provided regarding the state of the winding insulation:
● Is the winding head insulation conductively contaminated?
● Has the winding insulation absorbed moisture?
As such, you can determine whether the machine needs commissioning or any necessary
measures such as cleaning and/or drying the winding:
● Can the machine be put into operation?
● Must the windings be cleaned or dried?
Detailed information on testing and the limit values can be found here:
"Testing the insulation resistance and polarization index" (Page 51)
9.1.3
Inspections in the event of faults
Natural disasters or unusual operating conditions, such as overloading or short circuit, are
faults that overload the machine electrically or mechanically.
Immediately perform an inspection after such faults.
9.1.4
First service after installation or repair
Perform the following checks after approximately 500 operating hours or at the latest six
months after commissioning:
Table 9-1
Checks after assembly or repair
Check
When the
motor is
running
At stand‐
still
The stated electrical characteristics are being observed.
X
The permissible bearing temperatures are not exceeded (Page 98).
X
The smooth running characteristics and machine running noise have not
deteriorated.
X
The motor foundation has no cracks and indentations. (*)
X
X
(*) You can perform these checks while the motor is running or at a standstill.
Additional tests may also be required according to the system-specific conditions.
NOTICE
Machine damage
When carrying out the inspection, if you detect any impermissible deviations from the normal
state, you must rectify them immediately. They may otherwise cause damage to the machine.
Maintenance
9.1 Inspection and maintenance
SIMOTICS FD 1MQ1
124
Operating Instructions 01/2019
Содержание SIMOTICS FD 1MQ1
Страница 2: ...28 01 2019 14 14 V11 01 ...
Страница 48: ...Preparations for use 4 20 Converter operation SIMOTICS FD 1MQ1 48 Operating Instructions 01 2019 ...
Страница 108: ...Start up 7 11 Setting the motor parameters at the converter SIMOTICS FD 1MQ1 108 Operating Instructions 01 2019 ...
Страница 144: ...Maintenance 9 2 Corrective Maintenance SIMOTICS FD 1MQ1 144 Operating Instructions 01 2019 ...
Страница 166: ...Spare parts 10 19 Auxiliary terminal box 1XB302 SIMOTICS FD 1MQ1 166 Operating Instructions 01 2019 ...
Страница 170: ...Disposal 11 5 Disposal of components SIMOTICS FD 1MQ1 170 Operating Instructions 01 2019 ...
Страница 172: ...Service and Support SIMOTICS FD 1MQ1 172 Operating Instructions 01 2019 ...
Страница 176: ...Quality documents SIMOTICS FD 1MQ1 176 Operating Instructions 01 2019 ...
Страница 181: ......