6.5.11
Minimum air clearances
After proper installation, verify that the minimum air clearances between non-insulated parts
are maintained. Be aware of any protruding wire ends.
Table 6-4
Minimum air clearance dependent on rms value of the alternating voltage U
rms
Rms value of the alternating voltage V
rms
Minimum air clearance
≤ 500 V
8 mm
≤ 630 V
10 mm
≤ 800 V
12 mm
≤ 1000 V
14 mm
≤ 1250 V
18 mm
Values apply at an installation altitude of up to 2000 m.
When determining the required minimum air clearance, the voltage value in the table may be increased
by a factor of 1.1, so that the rated input voltage range is taken into account during general use.
6.5.12
Finishing connection work
1. Before closing the terminal box, please check that:
– The electrical connections in the terminal box have been made in accordance with the
specifications above and tightened with the correct tightening torque.
– The machine is connected in such a way that it rotates in the direction specified.
– The inside of the terminal box is clean and free of any cable debris, dirt and foreign
bodies.
– All of the seals and sealing surfaces of the terminal box are intact and in a good condition.
– Any unused cable entries are sealed with glued-in ferrous or certified sealing elements.
The sealing elements can only be removed with a tool.
– The connecting cables are laid in an open arrangement, so that the cable insulation
cannot be damaged during operation.
2. Close the terminal box with the cover fixing screws, see chapter Tightening torques for
screw and bolt connections (Page 169).
See also
Mounting/removing the terminal box (Page 77)
Electrical connection
6.5 Inserting and routing the cables
SIMOTICS FD 1MM1
90
Operating Instructions 02/2019
Содержание SIMOTICS FD 1MM1 Series
Страница 2: ...05 02 2019 16 03 V11 01 ...
Страница 30: ...Description SIMOTICS FD 1MM1 30 Operating Instructions 02 2019 ...
Страница 50: ...Preparations for use 4 19 Converter operation SIMOTICS FD 1MM1 50 Operating Instructions 02 2019 ...
Страница 94: ...Electrical connection 6 6 Connecting the auxiliary circuits SIMOTICS FD 1MM1 94 Operating Instructions 02 2019 ...
Страница 142: ...Maintenance 9 2 Corrective Maintenance SIMOTICS FD 1MM1 142 Operating Instructions 02 2019 ...
Страница 166: ...Disposal 11 5 Disposal of components SIMOTICS FD 1MM1 166 Operating Instructions 02 2019 ...
Страница 168: ...Service and Support SIMOTICS FD 1MM1 168 Operating Instructions 02 2019 ...
Страница 172: ...Quality documents SIMOTICS FD 1MM1 172 Operating Instructions 02 2019 ...
Страница 177: ......