6.5.11
Minimum air clearances
After proper installation, verify that the minimum air clearances between non-insulated parts
are maintained. Be aware of any protruding wire ends.
Table 6-5
Minimum air clearance dependent on rms value of the alternating voltage U
rms
Rms value of the alternating voltage V
rms
Minimum air clearance
≤ 500 V
8 mm
≤ 630 V
10 mm
≤ 800 V
12 mm
≤ 1000 V
14 mm
≤ 1250 V
18 mm
Values apply at an installation altitude of up to 2000 m.
When determining the required minimum air clearance, the voltage value in the table may be increased
by a factor of 1.1, so that the rated input voltage range is taken into account during general use.
6.5.12
Finishing connection work
1. Before closing the terminal box, please check that:
– The electrical connections in the terminal box have been made in accordance with the
specifications above and tightened with the correct tightening torque.
– The machine is connected in such a way that it rotates in the direction specified.
– The inside of the terminal box is clean and free of any cable debris, dirt and foreign
bodies.
– All of the seals and sealing surfaces of the terminal box are intact and in a good condition.
– Any unused cable entries are sealed with glued-in ferrous or certified sealing elements.
The sealing elements can only be removed with a tool.
– The connecting cables are laid in an open arrangement, so that the cable insulation
cannot be damaged during operation.
2. Close the terminal box with the cover fixing screws, see chapter Tightening torques for
screw and bolt connections (Page 179).
See also
Mounting/removing the terminal box (Page 88)
Electrical connection
6.5 Inserting and routing the cables
SIMOTICS FD 1MH1
100
Operating Instructions 08/2017
Содержание SIMOTICS FD 1LL1
Страница 2: ...18 08 2017 17 24 V10 00 ...
Страница 32: ...Description 3 1 Comparison of IEC and GOST standards SIMOTICS FD 1MH1 32 Operating Instructions 08 2017 ...
Страница 58: ...Preparations for use 4 19 Converter operation SIMOTICS FD 1MH1 58 Operating Instructions 08 2017 ...
Страница 104: ...Electrical connection 6 6 Connecting the auxiliary circuits SIMOTICS FD 1MH1 104 Operating Instructions 08 2017 ...
Страница 120: ...Start up 7 10 Setting the motor parameters at the converter SIMOTICS FD 1MH1 120 Operating Instructions 08 2017 ...
Страница 176: ...Disposal 11 4 Disposal of components SIMOTICS FD 1MH1 176 Operating Instructions 08 2017 ...
Страница 178: ...Service and Support SIMOTICS FD 1MH1 178 Operating Instructions 08 2017 ...
Страница 182: ...Quality documents SIMOTICS FD 1MH1 182 Operating Instructions 08 2017 ...
Страница 187: ......