8.10.4
Water cooling faults
The following table shows the possible causes of and remedial measures for faults on water-
cooled machines.
Table 8-3
Cooling system faults
↓ Overheating
↓ Water leaking
Possible causes of faults
Remedial measures
X
Reduced cooling
Check the cooling water flow, increase the amount of cooling water if
necessary.
X
Cooling water flow rate too low
Consult the manufacturer. If the specified cooling water quality is ob‐
served, the cooling system is maintenance-free.
X
Inlet temperature too high
Set the correct upstream temperature.
X
Cooling water supply switched off
Switch on the cooling water supply.
X
Cooling water contains too many or unsuit‐
able antifreeze and corrosion-protection
agents
Use cooling water of the agreed quality.
X Leaks in the cooling system
Consult the manufacturer.
X Defective cooling water connection
Find the leak and seal it.
Operation
8.10 faults
SIMOTICS FD 1LH1
120
Operating Instructions 01/2019
Содержание SIMOTICS FD 1LH1
Страница 2: ...23 01 2019 19 26 V11 01 ...
Страница 28: ...Description SIMOTICS FD 1LH1 28 Operating Instructions 01 2019 ...
Страница 72: ...Assembly 5 5 Connecting the cooling water supply SIMOTICS FD 1LH1 72 Operating Instructions 01 2019 ...
Страница 122: ...Operation 8 10 faults SIMOTICS FD 1LH1 122 Operating Instructions 01 2019 ...
Страница 140: ...Maintenance 9 2 Corrective Maintenance SIMOTICS FD 1LH1 140 Operating Instructions 01 2019 ...
Страница 162: ...Disposal 11 5 Disposal of components SIMOTICS FD 1LH1 162 Operating Instructions 01 2019 ...
Страница 164: ...Service and Support SIMOTICS FD 1LH1 164 Operating Instructions 01 2019 ...
Страница 168: ...Quality documents SIMOTICS FD 1LH1 168 Operating Instructions 01 2019 ...
Страница 173: ......