Preparing for use
4.13 Converter operation
Standard motors SH 63 ... 355
40
Operating Instructions, 12/2018, A5E38483075A
4.13
Converter operation
4.13.1
Parameterizing the converter
●
If the design of the motor requires connection to a particular converter type, the rating
plate will contain corresponding additional information.
●
Correctly parameterize the converter. Parameterizing data can be taken from the
machine rating plates.
You can find parameter data here:
–
In the operating instructions for the converter.
–
In the SIZER engineering tool
–
In the SINAMICS Configuration Manuals.
–
For explosion-protected machines, also in the declaration of compliance with the order
2.1.
●
Do not exceed the specified maximum speed limit
n
max
. You can either find this on the
rating plate
n
max
or on the supplementary plate for converter operation as the highest
speed.
●
Check that the machine is cooled sufficiently for commissioning purposes.
4.13.2
Converter input voltage
The insulation system of SIMOTICS machines always complies with the requirements of
stress category C (IVIC C = high stress). If voltage peaks higher than those specified
according to IVIC C can occur, then please contact your Siemens partner:
●
For a line supply voltage (converter input voltage) up to max. 480 V, and when controlled
from a SINAMICS G/SINAMICS S converter with uncontrolled/controlled infeed: Comply
with the guidelines for configuring motor and converter.
●
For line voltages (converter input voltages) higher than 480 V, motors, which are ordered
for converter operation, have an appropriate insulation system.
●
Operation with a converter from another manufacturer: Comply with the permissible
voltage peaks according to IEC 60034-18-41 in accordance with stress category C,
dependent on the particular line voltage (converter input voltage) and the motor insulation
system.
NOTICE
Material damage caused by an excessively high supply voltage
The insulation system will be damaged if the supply voltage is too high for the insulation
system. This can completely destroy the machine.
•
Comply with the peak voltages as laid down in the guidelines above.
Содержание SIMOTICS DP series
Страница 1: ......
Страница 2: ......
Страница 62: ...Assembly 5 4 Installing the machine Standard motors SH 63 355 60 Operating Instructions 12 2018 A5E38483075A ...
Страница 86: ...Commissioning 7 2 Switching on Standard motors SH 63 355 84 Operating Instructions 12 2018 A5E38483075A ...
Страница 98: ...Operation 8 7 Deactivating Standard motors SH 63 355 96 Operating Instructions 12 2018 A5E38483075A ...
Страница 118: ...Maintenance 9 3 Corrective maintenance Standard motors SH 63 355 116 Operating Instructions 12 2018 A5E38483075A ...
Страница 140: ...Disposal 11 6 Disposal of components Standard motors SH 63 355 138 Operating Instructions 12 2018 A5E38483075A ...
Страница 150: ......