6.5.1
Type of conductor connection
Terminal board
Conductor
cross-
section
[mm²]
Connection with cable lug
DIN 46 234
Bend down the cable lug for the
connection.
... 25
Connection of an individual conduc‐
tor with terminal clamp
... 10
Connection of two conductors of
approximately the same thickness
with terminal clamp
... 25
①
Connecting bar
②
Line supply cable
③
Motor connecting cable
④
Cover plate
6.6
Connecting converters
NOTICE
Excessively high supply voltage
Material damage can occur if the supply voltage is too high for the insulation system.
SIMOTICS machines can be operated with SINAMICS G converters and SINAMICS S
converters (uncontrolled and controlled infeed) when maintaining the permissible peak
voltages.
Carefully observe the values in the following tables.
Rise times t
r
> 0.1 µs.
The insulation system of SIMOTICS machines corresponds to the specifications laid down in
IEC 60034-18-41 according to voltage stress category C (IVIC C = high stress).
Electrical connection
6.6 Connecting converters
1PC134, 1PC136 crane motors SH 132 ... 315
Operating Instructions, 02/2019, A5E43212221A
59