Tables, data records
3.3 Tables, PROFIBUS data records
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
153
3.3.1.4
Detailed messages of the slave diagnostics
The following table contains the detailed messages of the slave diagnostics for status
information and the hardware interrupt. This information is also contained in data record 92.
Note
Structure of the slave diagnostics
The diagnostic messages listed below are the same as those contained in the hardware
interrupts transferred via PROFIBUS. See also Chapter "Structure of the slave
diagnostics
→
Hardware interrupt - Structure" in the SIMOCODE pro – System Manual
https://support.industry.siemens.com/cs/ww/en/view/109743957
Table 3- 22 Detailed messages of the slave diagnostics
Byte.Bit
Status message
Information
0.0
Faults - control
Fault - execution ON command
BU0 BU1 BU2(+)
0.1
Fault - execution STOP command
BU0 BU1 BU2(+)
0.2
Fault - feedback (FB) ON
BU0 BU1 BU2(+)
0.3
Fault - feedback (FB) OFF
BU0 BU1 BU2(+)
0.4
Fault - stalled positioner
BU2(+)
0.5
Fault - double 0
BU2(+)
0.6
Fault - double 1
BU2(+)
0.7
Fault - end position
BU2(+)
1.0
Fault - antivalence
BU2(+)
1.1
Fault - Cold start (TPF) fault
BU0 BU1 BU2(+)
1.2
Fault - power failure (UVO)
BU2(+)
1.3
Fault - Operational Protection Off (OPO)
BU2(+)
1.4
Reserved
2.0
Reserved
2.1
Faults - Protection
Fault - unbalance
IM UM
2.2
Fault - overload
IM UM
2.3
Fault - ov phase failure
IM UM
2.4
Fault - int. ground fault
IM UM
2.5
Fault - ext. ground fault
EM
2.6
Reserved
2.7
Fault - thermistor overload
Th
3.0
Fault - thermistor short circuit
Th
3.1
Fault - thermistor open circuit
Th
3.2
Reserved
3.3
Fault - TM trip T>
TM MM
3.4
Fault - TM sensor fault
TM MM
3.5
Fault - TM out of range
TM MM
3.6
Fault - EM+ open circuit
MM EM+