Communication
2.3 Modbus communication
SIMOCODE pro - Communication
108
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Function code 43 - Read Device Identification
Function
The function "43/14 (0x2B/0x0E) Read Device Identification" enables identification of the
addressed device configuration.
Modbus identification data
The Modbus identification data are a representation of the device I&M0 data.
Table 2- 34 Assignment of the I&M0 for Modbus identification
Modbus object ID
SIRIUS device
information
Type
Mandatory/optional
Assignment of I&M0
Manufacturer
SIEMENS AG
ASCII string
Mandatory
Name of manufacturer
Article number
MLFB
ASCII string
Mandatory
FW version
Vx.x
ASCII string
Mandatory
Software revision
Internet address of the
manufacturer
Device-specific
ASCII string
Optional
-
Device family
Device-specific
ASCII string
Optional
-
Device subfamily
Device-specific
ASCII string
Optional
-
Name of the user
Device-specific
ASCII string
Optional