2 Error Messages
279
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
A.2
Error Messages
OSCOP P displays the following error messages if the communication to SIMEAS R-PMU is
active:
Message ID
Error/Message
Comment
800
Unknown command received
Firmware or OSCOP update recommended, contact
hotline if necessary
801
Incorrect password or command not
executable
Firmware or OSCOP update recommended, contact
hotline if necessary
802
Command not executed
Firmware or OSCOP update recommended, contact
hotline if necessary
803
Command executed with error status
Firmware or OSCOP update recommended, contact
hotline if necessary
804
Illegal or invalid command parameter
Firmware or OSCOP update recommended, contact
hotline if necessary
805
Command executed on inactive
recorder
Unable to execute command: Recorder not active or
parameterized.
807, 810 -
812
File access error
Query table of contents again and check if the record has
been deleted via ring buffer mode, contact hotline if
necessary
808
Directory access error
Contact hotline
814
Database query outside time range
There are no records/entries for the given interval.
815
Database transmission overwritten
by measure
The requested record of a continuous recorder was
overwritten in ring buffer mode.
818
Error during compilation of system
parameters
Firmware or OSCOP update recommended, contact
hotline if necessary
819
Error during compilation of DAU
parameters
Firmware or OSCOP update recommended, contact
hotline if necessary
820
Error during parameterization, file
does not contain system data
Firmware or OSCOP update recommended, contact
hotline if necessary
821
Parameterization error, slot not
occupied
Firmware or OSCOP update recommended, contact
hotline if necessary
822
Parameter file update error
Firmware or OSCOP update recommended, contact
hotline if necessary
823
Error during firmware update
Check the communication link, contact hotline if
necessary
824
Error setting system information
Firmware or OSCOP update recommended, contact
hotline if necessary
825
Data transmission canceled
-
830
Time setting via the PC interface is
not allowed with synchronization type
GPS
Time setting via the PC interface is not allowed with
synchronization type GPS/DCF77.
831
Time setting via the PC interface can
be performed only every 4 hours
Set a cycle time of at least 4 hours for automatic time
setting.
832
V2/V3 command rejected
You tried to access the SIMEAS R-PMU with device type
SIMEAS R
. Create a device in OSCOP P Parameterize
PC with device type
SIMEAS R-PMU
. This device type is
available in OSCOP P 6.60.
833
Incorrect password
Parameterize the correct password, refer to chapter
12.1. In general, the password may be overwritten in the
first 3 minutes after new start of the device.
Содержание SIMEAS R-PMU
Страница 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 40: ...5 5 4 Monophase Connection 40 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 210: ...14 14 4 Commissioning 210 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 274: ...18 18 4 Time Synchronization 274 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 290: ...5 Special Note Open Source Software 290 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 292: ...Literature 292 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...