18
18.2 Data Acquisition Units (DAU)
264
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
18.2
Data Acquisition Units (DAU)
DAU types
Measured value processing of the DAU types (in detail)
Table 18-6
DAU types
Type
Application
Number of channels
Measuring ranges
(overview)
VCDAU Recording of voltage,
current and binary signals
- 8 analog (4 voltage
and 4 current)
- 16 binary
V:
AC 1.5 V to AC 400 V
I:
AC 5 mA to AC 400 A
binary: Table 18-8
VDAU Recording of voltages and
binary signals
- 8 analog (voltage)
- 16 binary
V:
AC 1.5 V to AC 400 V
binary: Table 18-8
CDAU Recording of currents and
binary signals
- 8 analog (current)
- 16 binary
I:
AC 5 mA to AC 400 A
binary: Table 18-8
DDAU Recording of process
values and binary signals
- 8 analog (8 voltage
or 8 current)
- 16 binary
V:
DC ±1 V / DC ±10 V
(>40 k
Ω
/ >400 k
Ω)
I:
DC ±20 mA (50
Ω
)
binary: Table 18-8
BDAU Recording of binary signals
- 32 binary
binary: Table 18-8
Table 18-7
Measuring ranges and important parameters (without binary inputs)
Type
Measuring ranges / accuracy
Parameters
VCDAU
Voltage measuring range AC 1.5 V to AC 200 V
Accuracy
*
: ±0.25 % of measured value ±30 mV
Frequency behaviour: 3 Hz to 5,500 Hz (5 %)
Voltage measuring range AC 3 V to AC 400 V
Accuracy *: ±0.25 % of measured value ±30 mV
Frequency behaviour: 3 Hz to 5,500 Hz (5 %)
Entire current measuring range:
AC 5 mA to AC 400 A
Current measuring range AC 5 mA to AC 7 A
Accuracy *: ±0.5 % of measured value ±0.5 mA
Frequency behaviour: 3 Hz to 5,500 Hz (5 %)
Current measuring range: >AC 7 A to AC 200 A
Accuracy *: ±1.5 % of measured value ±100 mA
Frequency behaviour: 0 Hz to 5,500 Hz (5 %)
Current measuring range >AC 200 A to AC 400 A
Accuracy *: ±3.5 % of measured value
Frequency behaviour: 0 Hz to 5,500 Hz (5 %)
Impedance: >100 k
Ω
Overvoltage: 300 V max. for 5 s
Impedance: >200 k
Ω
Overvoltage: 600 V max. for 5 s
Содержание SIMEAS R-PMU
Страница 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 40: ...5 5 4 Monophase Connection 40 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 210: ...14 14 4 Commissioning 210 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 274: ...18 18 4 Time Synchronization 274 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 290: ...5 Special Note Open Source Software 290 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 292: ...Literature 292 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...