16
16.1 Technical Data of the SIMEAS R-PMU
250
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
16.1.5 Communication Interfaces
Slot 1 – CPU
LPT 1
Printer port, Centronics IEEE 1284
for connecting a laser printer
(PostScript level 2)
COM S
RS232 interface, at the front for connecting a
PC, service interface
19.2 kbit/s, 8N1
COM 1
RS232 interface, at the back
for connecting, e. g., a PC, modem
or star coupler
9.6 kbit/s to 115.2 kbit/s, 8N1
LAN (Ethernet)
IEEE 802.3
10Base-T/100Base-T
10/100 Mbps full / half duplex
Communication ports
OSCOP P communication
2010/TCP
SIMEAS R network trigger
6000/UDP
PDC/PMU communication
freely parameterizable
Default setting:
4712/TCP or 4713/UDP
16.1.6
Time Synchronization
Synchronization
Precision of GPS/DCF77 synchronization (not via Sync-Box):
incl. phases accuracy measuring system; typically: ±10 µs
Precision of minute pulse synchronization: ±100 ms
Precision of "Time setting" via OSCOP P:
in automatic mode, cycle time 4 hours: ±1 s
RTC drift: 30 ppm at 25
°
C
Current consumption, synchronization input 7B1/7B2 at DC 24 V: DC 2 mA
Timer requirements
Precision: 5 µs
Synchronization signal level or optical output with conversion via Sync-Transceiver 7KE6000-
8AK/L: DC 24 V
Pulse width DCF77 low pulse: 100 ms ±20 ms
Pulse width DCF77 high pulse: 200 ms ±20 ms
Pulse width minute pulse: 200 ms to 1000 ms
In the event of an antenna failure, the DCF77 signal is cut off
Time basis: UTC
Содержание SIMEAS R-PMU
Страница 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 40: ...5 5 4 Monophase Connection 40 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 210: ...14 14 4 Commissioning 210 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 274: ...18 18 4 Time Synchronization 274 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 290: ...5 Special Note Open Source Software 290 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 292: ...Literature 292 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...