12
12.6 Device Function
143
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
12.6
Device Function
The
Device Function
menu item contains the
Continuous Recorder
and
Fault Recorder
tabs.
Here you can define the device functions to be used or the measured values to be recorded with
the device. Furthermore, you can allocate storage space to each function.
Continuous recorder
Select the
Continuous Recorder
tab.
Figure 12-12 Device Function, Continuous Recorder tab
Activate the
Phasor
checkbox in the
Continuous Recorder
menu item to switch on the
continuous recorder for complex phasors and frequencies.
The
Cycle Time in s
defines the frequency of data recording.
The
Recorder Size in MB
defines the size of the physical memory area for the
Continuous Phasor Recorder (CPR).
Furthermore, you can parameterize the following long-term recorders under
Continuous
Mean Value Recorder
:
V, I, Sym
Continuous mean value recorder (CRR) and symmetrical components
f
Continuous mean value recorder for frequencies (CFR)
P, Q
Continuous mean value recorder for active and reactive power (CQR)
DC
Continuous mean value recorder for process variables (CDR)
Check the appropriate checkbox to select the function and enter the averaging times (in s)
and the allocated memory space in the corresponding boxes.
Averaging Time in s
Period of time (in seconds) during which a mean value is calculated and stored in the
memory.
Содержание SIMEAS R-PMU
Страница 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 40: ...5 5 4 Monophase Connection 40 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 210: ...14 14 4 Commissioning 210 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 274: ...18 18 4 Time Synchronization 274 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 290: ...5 Special Note Open Source Software 290 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 292: ...Literature 292 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...