![Siemens SIMATIC TIM 3V-IE DNP3 Скачать руководство пользователя страница 248](http://html.mh-extra.com/html/siemens/simatic-tim-3v-ie-dnp3/simatic-tim-3v-ie-dnp3_system-manual_1265391248.webp)
Diagnostics and upkeep
7.3 SINAUT diagnostics and service tool
TIM DNP3
248
System Manual, 12/2015, C79000-G8976-C253-04
Function group,
diagnostic function
(remarks)
Subscriber type
relevant for diag-
nostics
Called in
menu
Access over
STEP 7
project
Access us-
ing Accessi-
ble Nodes
TD7 communication configuration
check (configured data)
CPU
"
X
TD7onTIM diagnostics
TIM
"
X
SDB Viewer
CPU, TIM
"
X
X
Service functions
SINAUT
Download SDB
TIM
"
X
Firmware update
TIM
"
X
Repair
TIM
"
X
Message protocol diagnostics
Project
TIM message protocol
TIM
"
X
X
The diagnostic information is displayed only for SIMATIC CPU modules and SINAUT TIM modules.
7.3.2
STEP 7 diagnostics
Introduction
STEP 7 diagnostics involves the standard diagnostic functions of SIMATIC STEP 7. Over
and above SIMATIC installations, the STEP 7 diagnostics in the SINAUT diagnostics and
service tool provides information not only on the CPU modules but also information on the
TIM modules of a project. The functions in the SINAUT diagnostics and service tool that are
implemented on the TIM module:
●
CPU messages
●
Module information
●
Operating mode
●
Setting the time
7.3.2.1
CPU messages
Description of the functions
The
CPU messages
function is used to archive diagnostic messages entered by a CPU or
TIM module in its diagnostic buffer. Without archiving, messages in the ring buffer of the
CPU or TIM would be successively overwritten once the buffer is full.
The
CPU messages
function registers the PG used for diagnostics with one or more
modules. The modules then transfer all newly generated diagnostic messages to the
registered PG. The diagnostic messages of one or more modules are archive in a common
list on the PG. The archive is designed as a ring buffer. The oldest messages are overwritten
by newly arriving messages once the archive is full.
Содержание SIMATIC TIM 3V-IE DNP3
Страница 12: ...Table of contents TIM DNP3 12 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 298: ...Diagnostics and upkeep 7 3 SINAUT diagnostics and service tool TIM DNP3 298 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 306: ...Technical specifications 8 3 Current consumption and power loss TIM DNP3 306 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 311: ...Approvals TIM DNP3 System Manual 12 2015 C79000 G8976 C253 04 311 ...
Страница 312: ......
Страница 332: ...Accessories A 5 LTOP overvoltage protection modules TIM DNP3 332 System Manual 12 2015 C79000 G8976 C253 04 ...