The SINAUT Configuration Tool
6.6 TD7onTIM
TIM DNP3
200
System Manual, 12/2015, C79000-G8976-C253-04
6.6.12
Data objects: Memory area and triggers of the channels
Enabling the channels of an object
When configuring the send and receive channels, you need to enable the individual channels
so that the transfer of data during operation is enabled for this channel. To allow this, each
channel of an object has the following option:
●
Channel active
Select this check box to enable the channel for data transfer.
If you are not sure whether or not you actually require a channel that has already had
parameters assigned or you want to block a channel later (possibly only temporarily), you
can disable it here without losing the parameters that have been entered.
If you do not require certain channels of a data object, ignore them and leave them without a
parameter assignment.
Memory area and triggers
With the two channel classes send channel and receive channel, apart from the object-
specific parameters, the following information is always configured:
●
For send channels:
–
Input address
Here, you specify the source address in the memory area of the CPU for the data to
be sent.
To send data to the communications partner, the TIM accesses this data area of its
local CPU.
–
Send trigger
Here, you specify whether the data transfer will be triggered and which trigger with
which setting will be used.
●
For receive channels:
–
Output address
Here you specify the destination address in the CPU memory for the received data.
The parameters are described below.
You can see examples of the parameter assignment dialogs in the two figures below.
Содержание SIMATIC TIM 3V-IE DNP3
Страница 12: ...Table of contents TIM DNP3 12 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 298: ...Diagnostics and upkeep 7 3 SINAUT diagnostics and service tool TIM DNP3 298 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 306: ...Technical specifications 8 3 Current consumption and power loss TIM DNP3 306 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 311: ...Approvals TIM DNP3 System Manual 12 2015 C79000 G8976 C253 04 311 ...
Страница 312: ......
Страница 332: ...Accessories A 5 LTOP overvoltage protection modules TIM DNP3 332 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 340: ...PG routing via WAN B 3 Preparations for PG routing TIM DNP3 340 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 350: ...Glossary TIM DNP3 350 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 354: ...Index TIM DNP3 354 System Manual 12 2015 C79000 G8976 C253 04 ...