Assigning Parameters to and Calling the S7-Graph FB
S7-GRAPH for S7 300/400 Programming Sequential Control Systems
9-14
C79000-G7076-C526-01
9.7.4
Automatic or Switch to next Mode (SW_TOP)
For initial project start up or for testing a control system step-by-step, the
"automatic or step-by-step" mode can be extremely useful:
•
The sequencer progresses when the transition is satisfied or when there is an
edge change from 0 to 1 at the parameter T_PUSH.
Input Parameters of the Automatic or Switch to next Mode
Parameters not listed are not mode-dependent.
Parameter
Data
Description
OFF_SQ
BOOL
All steps are immediately deactivated, in other
words "Sequencer Off"
INIT_SQ
BOOL
Initialize sequencer, jump to initial step
ACK_EF
BOOL
Acknowledgment of a disturbance
S_PREV
BOOL
As for automatic
S_NEXT
BOOL
As for automatic
SW_AUTO
BOOL
Request the automatic mode
SW_MAN
BOOL
Request manual mode
SW_TAP
BOOL
Request inching mode
T_PUSH
BOOL
The transition switches when there is a rising
edge at T_PUSH regardless of whether the
transition is satisfied.
Output Parameters of the Automatic or Switch to next Mode
Parameter
Data
Description
S_NO
INT
Step number, indicates the selected step
S_MORE
BOOL
Further active steps exist and can be indicated
in S_NO
S_ACTIVE
BOOL
The indicated step is active
ERR_FLT
BOOL
Error/disturbance occurred
AUTO_ON
BOOL
The automatic mode is not active
TAP_ON
BOOL
Inching mode is not active
MAN_ON
BOOL
Manual mode is not active
TOP_ON
BOOL
Automatic or switch to next mode is activated