Fail-Safe Blocks
Fail-Safe Systems
A5E00085588-03
8-49
8.5.2 F_R_BO
Function
This block safely receives 10 data items of the data type F_BOOL sent from
another F-run-time group from the F_S_BO block.
The received data is stored at the outputs RD_BO_xx for further processing by
other blocks.
The input S_DB must be connected with the output of the same name of the
sending block.
The input TIMEOUT must be assigned a value for monitoring the safety-related
communication. If an updated frame is not received during this time, the system
function SFC F_CTRL is called. See "Monitoring Safety-Related Communication
Between F Run-Time Groups".
Startup Characteristics
In the first cycle after a cold or warm restart, the block outputs the substitute values
configured at the SUBBO_xx inputs. The output of the substitute values depends
on the configured execution times of the cyclic interrupts and occurs as long as the
value F_TRUE is at the output SUBS_ON, but only until the monitoring time
TIMEOUT elapses.
I/Os
Name
Data Type
Explanation
Default
Inputs:
TIMEOUT
F_TIME
Monitoring time in ms for vital-
sign monitoring
T#0 ms
S_DB
F_WORD
Instance DB no. of the
associated F_S_BO
0
SUBBO_00
F_BOOL
Substitute value for receipt
data 00
0
...
...
SUBBO_09
F_BOOL
Substitute value for receipt
data 09
0
Outputs:
SUBS_ON
F_BOOL
Substitution values are output
0
RD_BO_00
F_BOOL
Receipt data 00
0
...
...
RD_BO_09
F_BOOL
Receipt data 09
0
Содержание SIMATIC S7 F
Страница 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Страница 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Страница 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Страница 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Страница 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Страница 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Страница 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Страница 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Страница 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Страница 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Страница 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...