Safety
Fail-Safe Systems
A5E00085588-03
7-11
7.4.2.2 Monitoring Safety-Related Communication Between the F-CPU
and F-I/Os
PROFIsafe time monitoring is executed in the F-I/Oand F driver with the same
PROFIsafe monitoring time. The value is entered in HWCONFIG as the monitoring
time of the F-I/O and assigned (monitoring time) and automatically assigned to the
F drivers at compilation (TIMEOUT).
To ensure that monitoring is not triggered in either the F driver or the F-I/O when
there are no faults, the PROFIsafe monitoring time TPSTO selected must be
sufficiently long:
TPSTO > 2* TTR + TF-I/O, ACK + MAX(TCImax ; TCI + TDP_FD) +
TSLAVE_SO + 2* TDP_DLY
Note the following:
Time
Description
Where to Find it?
TCI
Configured cycle time of
the cyclic interrupt OB
HWCONFIG
CPU properties, "Cyclic Interrupt,
Execution"
TCImax
Maximum cycle time of the
relevant cyclic interrupt OB
Monitoring the F Cycle Time section
TTR
Max. target rotation time
for the DP master system
Properties of the DP master system,
bus parameters in HWCONFIG
TDP_FD
Max. DP fault detection
time
Properties of the DP master system,
bus parameters, "H Parameters" tab
in HWCONFIG
TDP_SO
Max. DP switchover time
Properties of the DP master system,
bus parameters, "H Parameters" tab
in HWCONFIG
TSLAVE_SO
Maximum switchover time
for the active
communication channel in
a switched I/O system
In the technical specifications of the
switched DP slave (ET 200M)
TF-I/O, ACK
Maximum acknowledgment
time of the F-I/Oin safety
mode
You can find this time in the technical
specifications of the fail-safe I/O
manuals.
TDP_DLY
Additional DP Delay Time,
External DP Interface (DP)
Properties of the External DP
Interface (CP), “Operating Mode tab in
HWCONFIG.
Содержание SIMATIC S7 F
Страница 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Страница 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Страница 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Страница 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Страница 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Страница 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Страница 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Страница 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Страница 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Страница 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Страница 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...