Programming
Fail-Safe Systems
5-18
A5E00085588-03
Drivers for the F-I/Os in Standard Mode
If you use the F-I/Os in standard mode, you can use the standard channel drivers
from the PCS 7 Driver Blocks library.
Rules for F-Driver Blocks
•
The VALUE I/O of the F channel driver must be interconnected with the
symbolic address of the channel. In the case of redundant channels, the
VALUE I/O must be interconnected with the symbolic address of the channel
with the lower address .
•
A fail-safe signal on the ACK_REI input of each channel driver is required to
reintegrate an input or output channel. The signal must come from a fail-safe
digital input module or – via the F_QUITES F block – from an ES or OS.
•
Sequence: See Defining the Run Sequence.
Prerequisite
Symbolic names: Enter a symbolic name for each channel used. You must
allocate this name to the VALUE I/O of the associated F channel driver. We
recommend, for the sake of clarity, that you also enter the unused channels in the
symbol table as reserved or not used.
Procedure
When working with F-driver blocks, proceed as follows:
1.
Insert the correct F channel driver for each configured input/output channel.
You only have to insert one F channel driver for each pair of redundant
channels.
2.
Interconnect the VALUE I/O in each F channel driver with the symbolic name
of the associated channel. This step is required for all F channel drivers
placed. In the case of redundant modules, interconnect the VALUE I/O with the
lower channel address.
3.
Interconnect the following with the required signals:
- the I inputs of the F channel drivers F_CH_DO
- the Q outputs of the F channel drivers F_CH_DI
- the V outputs of the F channel drivers F_CH_AI
These I/Os are F_BOOL or F_REAL types and should only be interconnected with I/Os of
the same type belonging to other fail-safe blocks.
4.
Set the relevant ACK_NEC input to "1" if user acknowledgment is required with
automatic reintegration of the channel. The ACK_NEC input is preset with "0"
(optional, see "Passivation and Reintegration").
5.
Optional: Evaluate the ACK_REQ output in the standard program or on the OS
to find out if user acknowledgment is required.
Содержание SIMATIC S7 F
Страница 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Страница 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Страница 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Страница 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Страница 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Страница 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Страница 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Страница 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Страница 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Страница 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Страница 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...