General technical specifications
5.2 Standards Compliance
EIP-200S Ethernet/IP Adapter Distributed I/O System
System Manual, 06/2018, A5E44345053-AB
95
Environmental conditions
Table 5- 4
Transport and storage
Environmental conditions - Transport and storage
EN 60068-2-2, Test Bb, Dry heat and
EN 60068-2-1, Test Ab, Cold
-40° C to +70° C
EN 60068-2-30, Test Db, Damp heat
25° C to 55° C, 95% humidity
EN 60068-2-14, Test Na, temperature shock
-40° C to +70° C, dwell time 3 hours, 5 cycles
EN 60068-2-32, Free fall
0.3 m, 5 times, product packaging
Atmospheric pressure
1080 to 660h Pa (corresponding to an altitude of -1000 to 3500m)
Table 5- 5
Operating conditions
Environmental conditions - Operating
Ambient temperature range
(Inlet Air 25 mm below unit)
-0° C to 60° C horizontal mounting
-0° C to 50° C vertical mounting
95% non-condensing humidity
Unless otherwise specified
Atmospheric pressure
1080 to 795 hPa (corresponding to an altitude of -1000 to 2000m)
Concentration of contaminants
S0
2
: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% non-condensing
EN 60068-2-14, Test Nb, temperature change
5° C to 55° C, 3° C/minute
EN 60068-2-27 Mechanical shock
15 G, 11 ms pulse, 6 shocks in each of 3 axis
EN 60068-2-6 Sinusoidal vibration
DIN rail mount: 3.5 mm from 5-9 Hz, 1G from 9 to 150 Hz
Panel Mount: 7.0 mm from 5-9 Hz, 2G from 9 to 150 Hz
10 sweeps each axis, 1 octave per minute
Table 5- 6
High potential isolation test
High potential isolation test
24 V/5 V nominal circuits
115/230 V circuits to ground
115/230 V circuits to 115/230 V circuits
115 V/230V circuits to 24 V/5 V circuits
Ethernet port to 24V/5V circuits and ground
1
520 VDC (type test of optical isolation boundaries)
1500 VAC
1500 VAC
1500 VAC (3000 VAC / 4242 VDC type test)
1500 VAC (type test only)
1
Ethernet port isolation is designed to limit hazard during short term network faults to hazardous voltages. It does not
conform to safety requirements for routine AC line voltage isolation.
Protection class
Protection Class II according to EN 61131-2 (Protective conductor not required)