Special functions of a CPU 41x-H
6.3 Resetting the CPU to the factory state
S7-400H
System Manual, 03/2012, A5E00267695-11
81
6.3
Resetting the CPU to the factory state
CPU factory settings
A general memory reset is performed when you reset the CPU to its factory settings and the
properties of the CPU are set to the following values:
Table 6- 2
CPU properties in the factory settings
Properties
Value
MPI address
2
MPI transmission rate
187.5 Kbps
Contents of the diagnostic buffer
Empty
IP parameters
None
IP parameters
Default values
Operating hours counter
0
Date and time
01.01.94, 00:00:00
Procedure
Proceed as follows to reset a CPU to its factory settings:
1.
Switch off the mains voltage.
2.
If a memory card is inserted in the CPU, always remove the memory card.
3.
Hold the toggle switch in the MRES setting and switch the mains voltage on again.
4.
Wait until LED pattern 1 from the following overview is displayed.
5.
Release the toggle switch, set it back to MRES within 3 seconds and hold it in this
position.
After approx. 4 seconds all the LEDs light up.
6.
Wait until LED pattern 2 from the following overview is displayed.
This LED pattern lights up for approximately 5 seconds. During this period you can abort
the resetting procedure by releasing the toggle switch.
7.
Wait until LED pattern 3 from the following overview is displayed, and release the toggle
switch again.
The CPU is now reset to its factory settings. It starts without buffering and goes to STOP
mode. The event "Reset to factory setting" is entered in the diagnostic buffer.
Note
Canceling the operation
If the described operation is canceled prematurely and the CPU remains in an undefined
state, you can once again set it to a defined state by cycling power off and on.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...