Communication
14.1 Communication services
S7-400H
System Manual, 03/2012, A5E00267695-11
227
14.1.9
Open Communication Via Industrial Ethernet
Availability
S7-400H CPUs with firmware version 6.0 support "open communication over Industrial
Ethernet" (in short: open IE communication). The CPUs must also be configured accordingly
with this or a higher firmware version.
Functionality
The following services are available for open IE communication:
●
Connection-oriented protocols:
Prior to data transmission connection-oriented protocols establish a logical connection to
the communication partner and close this again, if necessary, after transmission is
completed. Connection-oriented protocols are used when security is especially important
in data transmission. A physical cable can generally accommodate several logical
connections. The maximum job length is 32 KB.
The following connection-oriented protocols are supported for the FBs for open IE
communication:
–
TCP to RFC 793
–
ISO on TCP according to RFC 1006
Note
ISOonTCP
For data communication with third-party systems via RFC1006, the connection partner
must adhere to the maximum TPDU size (TPDU = Transfer Protocol Data Unit)
negotiated in the ISOonTCP connection establishment.
●
Connectionless protocols:
Connectionless protocols operate without a logical connection. There is also no
establishing or terminating a connection to remote partner. Connectionless protocols
transfer the data unacknowledged and thus unsecured to the remote partner. The
maximum message frame length is 1472 bytes.
The following connectionless protocols are supported for the FBs for open
communication by means of Industrial Ethernet:
–
UDP according to RFC 768
The single-cast and broadcast modes are supported.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...