Using I/Os in S7–400H
13.3 Using single-channel switched I/O
S7-400H
System Manual, 03/2012, A5E00267695-11
173
13.3
Using single-channel switched I/O
What is single-channel switched I/O?
In the single-channel switched configuration, the input/output modules are present singly
(single-channel).
In redundant mode, these can addressed by both subsystems.
In standalone mode, the master subsystem can always address all switched I/Os (in contrast
to one-sided I/O).
Single-channel switched I/O configuration at the PROFIBUS DP interface
The system supports single-channel switched I/O configurations containing an ET 200M
distributed I/O module with active backplane bus and a redundant PROFIBUS DP slave
interface module.
6+DXWRPDWLRQV\VWHP
(7b0'LVWULEXWHG,2
5DFN
5DFN
Figure 13-1 Single-channel switched distributed I/O configuration at the PROFIBUS DP interface
You can use the following interfaces for the I/O configuration at the PROFIBUS DP interface:
Table 13- 1 Interfaces for use of single-channel switched I/O configuration at the PROFIBUS DP
interface
Interface
Order number
IM 153–2
6ES7 153–2BA81–0XB0
6ES7 153–2BA02–0XB0
6ES7 153–2BA01–0XB0
6ES7 153–2BA00–0XB0
IM 153–2FO
6ES7 153–2AB02–0XB0
6ES7 153–2AB01–0XB0
6ES7 153–2AB00–0XB0
6ES7 153–2AA02–0XB0
Each S7–400H subsystem is interconnected with one of the two DP slave interfaces of the
ET 200M via a DP master interface.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...