S7-400H
System Manual, 03/2012, A5E00267695-11
169
Using I/Os in S7–400H
13
This section provides an overview of the different I/O installations in the S7-400H automation
system and their availability. It also provides information on configuration and programming
of the selected I/O installation.
13.1
Introduction
I/O installation types
In addition to the power supply module and CPUs, which are always redundant, the
operating system supports the following I/O installations:
Configuration
Availability
Single-channel one-sided
Single-channel switched
System redundant
Dual-channel redundant
normal
enhanced
enhanced
high
A dual-channel redundant configuration at user level is also possible. You nevertheless need
to implement the high availability in the user program (see section Other options for
connecting redundant I/Os (Page 207)).
Addressing
No matter whether you are using a single-channel one-sided or switched I/O, you always
access the I/O via the same address.
Limits of I/O configuration
If there are insufficient slots in the central racks, you can add up to 20 expansion units to the
S7-400H configuration.
Module racks with even numbers are always assigned to central rack 0, and racks with odd
numbers are always assigned to central rack 1.
For applications with distributed I/O, each of the subsystems supports the connection of up
to 12 DP master systems (2 DP master systems on the integrated interfaces of the CPU and
10 via external DP master systems).
The integrated MPI/DP interface supports the operation of up to 32 slaves. You can connect
up to 125 distributed I/O devices to the integrated DP master interface and to the external
DP master systems.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...