System and operating states of the S7–400H
11
This chapter features an introduction to the subject of S7-400H fault-tolerant systems.
You will learn the basic terms that are used in describing how fault-tolerant systems operate.
Following that, you will receive information on fault-tolerant system states. They depend on
the operating states of the different fault-tolerant CPUs, which will be described in the next
section.
In describing these operating states, this section concentrates on the behavior that differs
from a standard CPU. You will find a description of the standard behavior of a CPU in the
corresponding operating mode in the
Programming with STEP 7 manual.
The final section provides details on the modified time response of fault-tolerant CPUs.
11.1
Introduction
The S7-400H consists of two redundantly configured subsystems that are synchronized via
fiber-optic cables.
Both subsystems create a fault-tolerant automation system operating with a two-channel (1-
out-of-2) structure based on the "active redundancy" principle.
What does active redundancy mean?
Active redundancy means that all redundant resources are constantly in operation and
simultaneously involved in the execution of the control task.
For the S7-400H this means that the user programs in both CPUs are identical and executed
synchronously by the CPUs.
Convention
To identify the two subsystems, we use the traditional expressions of "master" and "reserve"
for dual-channel fault-tolerant systems in this description. The reserve always processes
events in synchronism with the master, and does not explicitly wait for any errors before
doing so.
The distinction made between the master and reserve CPUs is primarily important for
ensuring reproducible error reactions. For example, the reserve CPU may go into STOP
when the redundant link fails, while the master CPU remains in RUN.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...