Digital modules
8.3 SM 326; DI 24 x DC 24V
Fail-safe signal modules
76
Installation and Operating Manual, 01/2010, A5E00085586-10
8.3
SM 326; DI 24 x DC 24V
8.3.1
Properties, Front View, Connection Diagram, and Block Diagram
Order number
6ES7326-1BK02-0AB0
Properties
SM 326; DI 24 x DC 24V has the following properties:
●
24 inputs, electrically isolated groups of 12 inputs
●
Rated input voltage 24 V DC
●
Suitable for switches and 2-/3-/4-wire proximity switches (BEROs)
●
Four short circuit-proof sensor supplies for each of the 6 channels, electrically
isolated in groups of 2
●
External sensor supply possible
●
Group fault display (SF)
●
Safety mode display (SAFE)
●
Status display for each channel (green LED)
●
Configuration in Run (CiR) supported in standard mode (non-safety mode)
●
Programmable diagnostics functions
●
Assignable diagnostic interrupt
●
Supports operation in standard and safety mode
●
SIL3/Cat.4/PLe can be achieved without safety protector
●
1oo1 and 1oo2 evaluation can be configured separately for each channel
●
Simplified PROFIsafe address assignment
●
I&M identification data
●
can be used with PROFINET IO
●
supports time stamping
●
Acknowledgment possible after voltage dip
Note
The fail-safe performance characteristics in the technical data apply to a proof-test interval of
10 years and a mean time to repair of 100 hours.
Содержание Simatic S7-300
Страница 326: ...Response times D 1 Response Times Fail safe signal modules 326 Installation and Operating Manual 01 2010 A5E00085586 10 ...
Страница 344: ...Glossary Fail safe signal modules 344 Installation and Operating Manual 01 2010 A5E00085586 10 ...
Страница 356: ...Product Information 4 A5E03004206 01 ...