![Siemens Simatic S7-300 Скачать руководство пользователя страница 161](http://html.mh-extra.com/html/siemens/simatic-s7-300/simatic-s7-300_installation-and-operating-manual_374640161.webp)
Digital modules
8.7 SM 326; F-DO 10 x DC 24V/2A PP (6ES7326-2BF10-0AB0)
Fail-safe signal modules
Installation and Operating Manual, 01/2010, A5E00085586-10
161
8.7
SM 326; F-DO 10 x DC 24V/2A PP (6ES7326-2BF10-0AB0)
8.7.1
Properties, front view, wiring diagram and block diagram
Order number
6ES7326-2BF10-0AB0
Properties
SM 326; F-DO 10 x DC 24V/2A PP has the following properties:
●
10 outputs, two electrically isolated groups of 5
●
Output current 2 A
●
Rated load voltage 24 V DC
●
Protection against short circuit and overload
●
Suitable for solenoid valves, DC relay contactors, and signal lamps
●
Assignable redundant operation
●
Operation in safety mode
●
SIL3/Cat.4/PLe can be achieved without safety protector
●
Group fault display (SF)
●
Safety mode display (SAFE)
●
Status display for each channel (green LED)
●
Display of channel-specific errors (red LED)
●
Programmable diagnostics functions
●
Programmable diagnostic interrupt
●
Firmware update via
HW Config
●
I&M identification data
●
can be used with PROFINET IO
●
"Keep last valid value" parameter
●
Simplified redundant circuit
●
Channel-selective passivation
Note
The fail-safe performance characteristics in the technical data apply to a proof-test interval of
20 years and a mean time to repair of 100 hours.