Digital modules
8.3 SM 326; DI 24 x DC 24V
Fail-safe signal modules
102
Installation and Operating Manual, 01/2010, A5E00085586-10
8.3.10
Technical data - SM 326; DI 24 x DC 24V
Overview
Technical data
Dimensions and Weight
Dimensions W x H x D (mm)
80 x 125 x 120
Weight
Approx. 442 g
Module-Specific Specifications
Configuration in Run (CiR) supported
Yes (only in standard mode)
Behavior of non-configured inputs during CiR Return the process value that was valid prior to
parameter assignment
Supports time stamping
Yes
Accuracy
20 ms to 30 ms
Number of inputs
Single-channel
24
Dual-channel
12
Assigned address area
In the I/O input area
10 bytes
In the I/O output area
4 bytes
Cable length
Unshielded
100 m, maximum
Shielded
200 m, maximum
Front connectors
40-pin
Maximum achievable Safety Integrity Level in safety mode
According to IEC 61508
SIL 3
According to EN 954-1
Category 4
According to ISO 13849:2006
PLe
Fail-safe performance characteristics
SIL 2
SIL 3
low demand mode (average probability of
failure on demand)
< 1.00E-04
< 1.00E-05
high demand / continuous mode (probability
of a dangerous failure per hour)
< 1.00E-08
< 1.00E-09
Voltages, Currents, Potentials
Rated supply voltage of the electronic system
and sensors 1L+, 2L+
24 V DC
Reverse polarity protection
Yes
Power failure ride-through (does not apply to
sensor supply outputs)
5 ms