Testing functions, Diagnostics and Fault Elimination
S7-300 Programmable Controller Hardware and Installation
10-22
A5E00105492-01
10.6.4
Structure of slave diagnostic data
Structure of slave diagnostic data
The figure below shows the structure of the diagnostics message frame for slave
diagnostics.
Station status 1 to 3
Byte 0
Byte 1
Byte 2
Byte 3
Master PROFIBUS address
Byte 4
Byte 5
Low-Byte
High-Byte
Manufacturer ID
Byte 6
to
Module diagnostics
Byte x-1
.
.
.
length depends on the number of
the configured areas of the
Intermediate memory)
1
1
Exception: if the
is wrongly configured,
DP master
the DP slave will interprete 35 configured address areas
(46 in byte 6)
.
.
.
Modul status (device-specific diagnostics)
Byte x+1
to
Byte y-1
length depends on the number
of the configured address areas)
.
.
.
Interrupt status (device-specific diagnostics)
Byte y
to
Byte z
(length depends on
interrupt type)
H
Figure 10-7 Structure of slave diagnostic data
Содержание Simatic S7-300
Страница 10: ...Contents S7 300 Programmable Controller Hardware and Installation x A5E00105492 01 ...
Страница 16: ...Preface S7 300 Programmable Controller Hardware and Installation 1 6 A5E00105492 01 ...
Страница 22: ...Quick Guide S7 300 Programmable Controller Hardware and Installation 2 6 A5E00105492 01 ...
Страница 28: ...Product overview S7 300 Programmable Controller Hardware and Installation 3 6 A5E00105492 01 ...
Страница 74: ...Configuring S7 300 Programmable Controller Hardware and Installation 4 46 A5E00105492 01 ...
Страница 102: ...Wiring S7 300 Programmable Controller Hardware and Installation 6 18 A5E00105492 01 ...
Страница 148: ...Commissioning S7 300 Programmable Controller Hardware and Installation 8 36 A5E00105492 01 ...
Страница 236: ...Glossary S7 300 Programmable Controller Hardware and Installation 12 16 A5E00105492 01 ...