Commissioning
S7-300 Programmable Controller Hardware and Installation
A5E00105492-01
8-29
8.7.3
Commissioning the CPU as DP slave
Prerequisites for commissioning
•
The DP master is configured and programmed.
•
If the MPI/DP interface of CPU 318-2 DP is to be operated as DP interface, you must
configure the interface accordingly.
•
You must program and configure CPU 31x-2 DP/31xC-2 DP as DP slave prior to
commissioning. That is, in STEP 7 you must:
–
"switch on" the CPU as DP slave,
–
assign a PROFIBUS address to the CPU,
–
assign a slave diagnostic address to the CPU,
–
specify whether the DP master is an S7 DP master or another DP master,
–
specify the address areas for data exchange with the DP master.
•
All other DP slaves are programmed and configured.
GSD Files
When working on an IM 308-C or non-Siemens system, you require a GSD file in
order to be able to configure CPU 31x-2 DP/31xC-2 DP as DP slave in a DP
master system.
COM PROFIBUS
as of V 4.0 includes this GSD file.
When working with an older version or another configuration tool, you can
download the GSD file under:
•
Internet URL http://www.ad.siemens.de/csi/gsd
or
•
via modem from the SSC (Interface Center) Fürth, Germany; Phone number (0911)
911/737972
Configuration and parameter assignment message frame
STEP 7
supports you in configuring/programming CPU 31x-2 DP/31xC-2 DP.
Should you require a description of the configuration and parameter assignment
frame, in order to use a bus monitor for example, you can find it on the Internet at
http://www.ad.siemens.de/csinfo under article ID 1452338.
Содержание Simatic S7-300
Страница 10: ...Contents S7 300 Programmable Controller Hardware and Installation x A5E00105492 01 ...
Страница 16: ...Preface S7 300 Programmable Controller Hardware and Installation 1 6 A5E00105492 01 ...
Страница 22: ...Quick Guide S7 300 Programmable Controller Hardware and Installation 2 6 A5E00105492 01 ...
Страница 28: ...Product overview S7 300 Programmable Controller Hardware and Installation 3 6 A5E00105492 01 ...
Страница 74: ...Configuring S7 300 Programmable Controller Hardware and Installation 4 46 A5E00105492 01 ...
Страница 102: ...Wiring S7 300 Programmable Controller Hardware and Installation 6 18 A5E00105492 01 ...
Страница 148: ...Commissioning S7 300 Programmable Controller Hardware and Installation 8 36 A5E00105492 01 ...
Страница 236: ...Glossary S7 300 Programmable Controller Hardware and Installation 12 16 A5E00105492 01 ...