![Siemens SIMATIC S7-300 FM 350-1 Скачать руководство пользователя страница 46](http://html.mh-extra.com/html/siemens/simatic-s7-300-fm-350-1/simatic-s7-300-fm-350-1_manual_1265384046.webp)
Programming the FM 350-1
5.2 The function FC CNT_CTL1 (FC 2)
FM 350-1 Counter module
46
Manual, 05/2011, A5E03648639-01
DB address
Parameters
Meaning
x = irrelevant
Bit 7
Bit 6
Bit 5
Bit 4
Reaction of output DO1
x
0
0
0
Inactive
x
0
0
1
Active from comparison value to overflow
x
0
1
0
Active from comparison value to underflow
x
0
1
1
Active on reaching the comparison value for pulse
duration (up/down)
x
1
0
0
Active on reaching the comparison value for pulse
duration (up)
x
1
0
1
Active on reaching the comparison value for pulse
duration (down)
x
1
1
0
Switch to comparison values
x = irrelevant
15.0
Hysteresis (range of values 0 to 255)
16.0
Pulse duration (value range 0 to 250)
17.0
Reserve = 0
18.0
CMP_V1
Comparison value 1; load with function parameter: T_CMP_V1
22.0
CMP_V2
Comparison value 2; load with function parameter: T_CMP_V2
Parameters for Transferring Values in the DB (Measuring Modes)
The following table shows the range of the DB in which you transfer the LOAD_VAL,
CMP_V1 and CMP_V2 parameters.
The LOAD_VAL parameter (bytes 14 to 17) has two meanings:
●
If you set function parameter L_PREPAR, LOAD_VAL is interpreted as a low limit
●
If you set function parameter C_DOPARA, Byte 14 is used to define the behavior of
Output DO0.
You must not set the L_DIRECT parameter for a measuring mode.
Содержание SIMATIC S7-300 FM 350-1
Страница 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Страница 168: ...Encoder signals and their evaluation 8 4 Signal evaluation FM 350 1 Counter module 168 Manual 05 2011 A5E03648639 01 ...
Страница 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Страница 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Страница 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Страница 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...