Definition of a diagnostics interrupt
You can determine reactions to internal or external errors in the user program, by
programming a diagnostics interrupt which interrupts cyclic program execution on the CPU,
and triggers a call of diagnostics interrupt OB 82.
Events which can trigger a diagnostics interrupt
The list shows which events can trigger a diagnostics interrupt:
●
Short-circuit or overload at the external auxiliary voltage 1L+/1M
●
Error at the 5.2 V DC encoder supply
●
No module configuration
●
Faulty module parameters
●
Watchdog timeout
●
RAM defective
●
Hardware interrupt lost
●
Signal A error (wire break, short-circuit, cable missing)
●
Signal B error (wire break, short-circuit, cable missing)
●
Signal N error (wire break, short-circuit, cable missing)
Enabling diagnostics interrupts
You disable or enable interrupts at the module, and define whether it should generate
diagnostics and/or a hardware interrupts using the programming interfaces.
Reactions to a diagnostics interrupt
Actions initiated when an event triggers a diagnostics interrupt:
●
The diagnostics information will be written to the diagnostics data records DS0 and DS1.
●
The group error LED is lit.
The group error LED does dark when the error is eliminated.
●
Call of the diagnostics interrupt OB 82.
●
The diagnostics data record DS0 will be written to the start information of the diagnostics
interrupt OB.
●
The count continues unchanged.
If no OB 82 is programmed, the CPU goes into STOP.
Содержание SIMATIC S7-300 FM 350-1
Страница 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Страница 168: ...Encoder signals and their evaluation 8 4 Signal evaluation FM 350 1 Counter module 168 Manual 05 2011 A5E03648639 01 ...
Страница 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Страница 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Страница 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Страница 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...