Encoder signals and their evaluation
8.4 Signal evaluation
FM 350-1 Counter module
Manual, 05/2011, A5E03648639-01
167
Double evaluation
Double evaluation refers to the evaluation of the positive and negative edges of signal A.
The logic level at signal B determines the count direction, i.e. the up or down count pulse.
The diagram shows the double evaluation of signals:
6LJQDO$$
6LJQDO%%
8SFRXQW
SXOVHV
'RZQFRXQW
SXOVHV
'RZQ
8S
Figure 8-5
Double evaluation
Quadruple evaluation
Quadruple evaluation refers to the evaluation of the positive and negative edges of signals A
and B. The logic level at the signals A and B determines the count direction, i.e. the up or
down count pulse.
The diagram shows quadruple evaluation of signals:
6LJQDO$$
6LJQDO%%
8SFRXQW
SXOVHV
'RZQFRXQW
SXOVHV
8S
'RZQ
Figure 8-6
Quadruple evaluation
Default
Single evaluation is set by default.
Содержание SIMATIC S7-300 FM 350-1
Страница 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Страница 168: ...Encoder signals and their evaluation 8 4 Signal evaluation FM 350 1 Counter module 168 Manual 05 2011 A5E03648639 01 ...
Страница 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Страница 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Страница 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Страница 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...