Encoder signals and their evaluation
8.4 Signal evaluation
FM 350-1 Counter module
166
Manual, 05/2011, A5E03648639-01
8.4
Signal evaluation
Overview
The counter module supports the count of signal edges. It usually evaluates the edge at A
(A*) (single evaluation). Options in the program of increasing the resolution:
●
Single evaluation
●
Double evaluation
●
Quadruple evaluation
Multiple evaluation is only supported for 5-V incremental encoders which return the A and B
signal with a phase shift of 90°, for 24-V incremental 24 V encoders with a phase shift of 90°
of the A* and B* signals.
Single evaluation
In this mode, the module evaluates only one edge of signal A. Up count pulses are recorded
at the positive edge at track A, and if track B is low. Down count pulses are recorded at the
positive edge at track A, and if track B is low.
The diagram shows a single evaluation of signals:
6LJQDO$$
6LJQDO%%
8SFRXQW
SXOVHV
'RZQFRXQW
SXOVHV
8S
'RZQ
Figure 8-4
Single evaluation
Содержание SIMATIC S7-300 FM 350-1
Страница 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Страница 168: ...Encoder signals and their evaluation 8 4 Signal evaluation FM 350 1 Counter module 168 Manual 05 2011 A5E03648639 01 ...
Страница 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Страница 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Страница 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Страница 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...