Operating Modes, parameters and commands
7.3 Count modes
FM 350-1 Counter module
Manual, 05/2011, A5E03648639-01
127
7.3.11
Command: Latch / retrigger
Introduction
The latch/retrigger command can be used to save (latch) counter values using the edges of
signals at digital input DI-Start. After each latching operation, the counter will be initialized
with the load value, and resumes the count starting at the load value (retrigger.)
Requirement
Set the SW gate to enable this command.
The minimum interval between latch edges is 1 ms. Values may be lost if this edge interval is
less than this time.
Selecting edge signals
You can assign the following behavior:
●
Latch/retrigger at the positive edge at DI-Start.
●
Latch/retrigger at the negative edge at DI-Start
●
Latch/retrigger at both edges at DI-Start