Communication via Function Blocks
6.5 Using the System Function Blocks with the ASCII Driver
CP 341 Point-to-Point Communication, Installation and Parameter Assignment
162
Manual, 09/2008, A5E02191071-01
FC 5 V24_STAT parameters
The following table lists the parameters of the FC 5 V24_STAT.
Table 6- 11 FC 5 V24_STAT parameters
Name
Sort
Data type
Comment
Permitted values, remark
LADDR
INPUT
INT
CP 341 start address
The start address is taken from
STEP 7.
DTR_OUT
OUTPUT
BOOL
Data terminal ready,
CP 341 ready for operation
(CP 341 output)
DSR_IN
OUTPUT
BOOL
Data set ready,
Communication partner ready for
operation
(CP 341 input)
RTS_OUT
OUTPUT
BOOL
Request to send,
CP 341 ready to send
(CP 341 output)
CTS_IN
OUTPUT
BOOL
Clear to send,
Communication partner can receive
data from the CP 341 (response to RTS
= ON of the CP 341)
(CP 341 input)
DCD_IN
OUTPUT
BOOL
Data Carrier detect,
receive signal level
(CP 341 input)
RI_IN
OUTPUT
BOOL
Ring Indicator,
Indication of incoming call
(CP 341 input)