Open loop motion control
12.5 Configuring an Axis of Motion
S7-200 SMART
System Manual, V2.3, 07/2017, A5E03822230-AF
609
Note
High-speed input wiring must use shielded cables
Use shielded cable with a maximum length of 50 m, when connecting HSC input channels
I0.0, I0.1, I0.2, and I0.3.
Mapping the I/O
STEP 7-Micro/WIN SMART enforces a fixed output assignment for PWM and Axis of Motion.
P0 and P1 outputs
At a minimum, any axis that is enabled has a P0 output pin configured for it. It may also have
P1 output if its "Phase" configuration is anything other than "Single-phase (1 output)". Refer
to the "Editing default input and output configuration" section for more information. These
output pins are hard-coded to a specific output, depending on the following criteria:
Axis 0
•
P0 for Axis 0 is always configured for Q0.0.
•
P1 for Axis 0 is configured for Q0.2 if the "Phase" for the axis is not configured to
"Single phase (1 output)".
Axis 1
•
P0 for Axis 1 is always configured for Q0.1.
•
P1 for Axis 1 is mapped in two possible locations based upon axis configuration as
follows:
–
If the "Phase" for Axis 1 is configured for "Single-phase (1 output)", then no P1
output is assigned.
–
If the "Phase" for Axis 1 is configured for "Two-phase (2 output)" or "AB quadra-
ture phase (2 output)", then P1 is configured for Q0.3.
–
Else, P1 for Axis 1 is configured for Q0.7.
Axis 2
•
P0 for Axis 2 is always configured for Q0.3.
•
P1 for Axis 2 is configured for Q1.0 if the "Phase" for the axis is not configured to
"Single phase (1 output)".
•
Axis 2 is not available for use if the configured "Phase" for Axis 1 is configured to
"Two-phase (2 output)" or "AB quadrature phase (2 output)".
DIS outputs
If an axis has a DIS output configured, then an entry is present in the mapping table for that
output. The DIS output is also hard-coded to specific outputs based upon the following rules:
●
DIS for Axis 0 is always configured for Q0.4.
●
DIS for Axis 1 is always configured for Q0.5.
●
DIS for Axis 2 is always configured for Q0.6.
Pulse output units are connected to standard 24V outputs.
Содержание SIMATIC S7-200
Страница 30: ...Product overview 1 7 Programming software S7 200 SMART 30 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 267: ...Program instructions 7 6 Counters S7 200 SMART System Manual V2 3 07 2017 A5E03822230 AF 267 HSC modes 3 and 4 ...
Страница 394: ...Program instructions 7 18 Subroutine S7 200 SMART 394 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 425: ...Communication 8 5 PROFIBUS S7 200 SMART System Manual V2 3 07 2017 A5E03822230 AF 425 ...
Страница 786: ...Technical specifications A 11 S7 200 SMART cables S7 200 SMART 786 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 798: ...Error codes C 4 PLC fatal error codes S7 200 SMART 798 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 848: ...Ordering information F 6 Human Machine Interface devices S7 200 SMART 848 System Manual V2 3 07 2017 A5E03822230 AF ...