Timer programming tips and examples
Timer types
You can use timers to implement time-based counting functions. The S7-200 instruction set
provides three different types of timers.
●
On-Delay Timer (TON) for timing a single interval
●
Retentive On-Delay Timer (TONR) for accumulating a number of timed intervals
●
Off-Delay Timer (TOF) for extending time past an off (or false condition), such as for
cooling a motor after it is turned off
Addressing timer values
The meaning of the T number depends on the context in your program.
●
"T37" assigned to a timer box identifies which timer is to use.
●
"T37" assigned to normally open contacts addresses the Boolean T37 timer bit.
●
"T37" assigned to integer operations addresses the T37 current time value, as a data
word.
1-millisecond resolution
The 1-ms timers count the number of 1-ms timer intervals that have elapsed since the active
1-ms timer was enabled. The execution of the timer instruction starts the timing; however,
the 1-ms timers are updated (timer bit and timer current) every millisecond asynchronous to
the scan cycle. In other words, the timer bit and timer current are updated multiple times
throughout any scan that is greater than 1 ms.
The timer instruction is used to turn the timer on, reset the timer, or, in the TONR timer, to
turn the timer off.
Since the timer can be started anywhere within a millisecond, the preset must be set to one
time interval greater than the minimum desired timer interval. For example, to guarantee a
timed interval of at least 56 ms using a 1-ms timer, the preset time value should be set to 57.
10-millisecond resolution
The 10-ms timers count the number of 10-ms timer intervals that have elapsed since the
active 10-ms timer was enabled. The execution of the timer instruction starts the timing;
however the 10-ms timers are updated at the beginning of each scan cycle (in other words,
the timer current and timer bit remain constant throughout the scan), by adding the
accumulated number of 10-ms intervals (since the beginning of the previous scan) to the
current value for the active timer.
Since the timer can be started anywhere within a 10-ms interval, the preset must be set to
one time interval greater than the minimum desired timer interval. For example, to guarantee
a timed interval of at least 140 ms using a 10-ms timer, the preset time value should be set
to 15.
Содержание SIMATIC S7-200
Страница 30: ...Product overview 1 7 Programming software S7 200 SMART 30 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 267: ...Program instructions 7 6 Counters S7 200 SMART System Manual V2 3 07 2017 A5E03822230 AF 267 HSC modes 3 and 4 ...
Страница 394: ...Program instructions 7 18 Subroutine S7 200 SMART 394 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 425: ...Communication 8 5 PROFIBUS S7 200 SMART System Manual V2 3 07 2017 A5E03822230 AF 425 ...
Страница 786: ...Technical specifications A 11 S7 200 SMART cables S7 200 SMART 786 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 798: ...Error codes C 4 PLC fatal error codes S7 200 SMART 798 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 848: ...Ordering information F 6 Human Machine Interface devices S7 200 SMART 848 System Manual V2 3 07 2017 A5E03822230 AF ...