5.6 Configuring the CPU for communication
S7-1200 Programmable controller
System Manual, 11/2011, A5E02486680-05
129
Table 5- 9
Parameters for the IP address
Parameter
Description
Subnet
Name of the Subnet to which the device is connected. Click the "Add new subnet" button to create a
new subnet. "Not connected" is the default. Two connection types are possible:
The "Not connected" default provides a local connection.
A subnet is required when your network has two or more devices.
IP address
Assigned IP address for the CPU
Subnet mask
Assigned subnet mask
Use IP router
Click the checkbox to indicate the use of an IP router
IP protocol
Router address
Assigned IP address for the router, if applicable
5.6.5
Testing the PROFINET network
After completing the configuration, download the project (Page 157) to the CPU. All IP
addresses are configured when you download the project.
Assigning an IP address to a device online
The S7-1200 CPU does not have a pre-configured IP address. You must manually assign an
IP address for the CPU:
●
To assign an IP address to a device online, refer to "Device configuration: Assigning an
IP address to a CPU online" (Page 125) for this step-by-step procedure.
●
To assign an IP address in your project, you must configure the IP address in the Device
configuration, save the configuration, and download it to the PLC. Refer to "Device
configuration: Configuring an IP address for a CPU in your project" (Page 127) for more
information.