2 Engineering
Securely Connecting RTU3041C to TeleControl Server Basic
Entry ID: 109739240, V3.0, 07/2021
76
©
S
iem
e
n
s A
G
2021
A
ll r
igh
ts
re
se
rv
e
d
2.2.5
Loading the Configuration File
The supplied archive
"109739240_RTU3041C_TCSB_SINEMA_RC_PROJ_V30.zip" contains the
finished configuration file ("*.cfg"), which you can load into your RTU and adapt to
your application in just a few steps.
To load the supplied configuration into your RTU3041C, proceed as follows:
1. Connect the RTU3041C to your PG/PC via a network cable.
Note
Ensure that only one RTU is connected to your network at a time during
commissioning, as each RTU is assigned the same IP address at the factory.
2. If necessary, change the IP address of your PG/PC (according to
) so
that it and the RTU3041C are in the same subnet.
The factory default IP address "
192.168.0.3
" is set in the RTU3041C.
3. Wake up the RTU3041C by briefly pressing the WKUP/RESET button on the
RTU.
4. In a browser, open the web server of the RTU3041C at the address
"
192.168.0.3
".
5. Log in with the username "admin" and the password "admin".
6. Assign a new username and password.
7. Navigate to the menu "Maintenance > Configuration".
8. Under "Load configuration", click "Search".
9. Select the downloaded configuration file.
10. Confirm with "Ok".