Application and functions
1.9 Performance data
RTU303xC
Operating Instructions, 06/2019, C79000-G8976-C382-06
37
Number of communications connections for productive data transfer
●
Configurable connections
The following number of connections can be configured as an alternative:
–
1 connection to the telecontrol server
–
1 connection to an ST7 master station (or node station)
–
1 connection to a DNP3 server
As an option, you can configure the connection to a second alternative master.
–
2 connections to an IEC master
The second connection is kept as redundant connection to a second master of a
redundancy group.
Also:
–
1 connection to an OpenVPN server or SINEMA RC server
If OpenVPN is used, a replacement server can optionally be configured.
–
Max. 1 connection to an FTP/FTPS server
–
Max. 1 connection to a mail server (extended SMTP)
●
Productive connections
In total the following connections can be established at the same time:
–
Max. 1 connection to a telecontrol server, an ST7 TIM, a DNP3 or IEC master
–
Max. 1 redundancy connection to an IEC master
–
Max. 1 connection to the VPN server
–
Max. 1 connection to an FTP/FTPS server
–
Max. 1 connection to a mail server (extended SMTP)
Number of HTTP/HTTPS connections for access to the WBM
●
Max. 2 HTTP connections at the same time
A configuration and firmware file cannot be loaded simultaneously via both WBM
sessions.
●
Max. 2 HTTPS connections at the same time via LAN
●
Max. 1 HTTPS connection at the same time via WAN
Number of connections to the WAN interface
A maximum of 6 connections can be established simultaneously at the WAN interface.
Possible connections at the WAN interface:
●
1 connection to a telecontrol server, an ST7-TIM, a DNP3 or IEC master (static)
●
1 redundancy connection to an IEC master (static)
●
1 connection to a VPN server (static)
Содержание Simatic RTU3030C
Страница 248: ...Configuration WBM 4 24 Tag tables RTU303xC 248 Operating Instructions 06 2019 C79000 G8976 C382 06 ...
Страница 350: ...Dimension drawings RTU303xC 350 Operating Instructions 06 2019 C79000 G8976 C382 06 Figure B 2 Side view ...
Страница 376: ...Accessories C 7 Overvoltage protection modules RTU303xC 376 Operating Instructions 06 2019 C79000 G8976 C382 06 ...
Страница 390: ...Documentation references E 10 10 RTU303xC 390 Operating Instructions 06 2019 C79000 G8976 C382 06 ...