Application and functions
1.9 Performance data
RTU303xC
36
Operating Instructions, 06/2019, C79000-G8976-C382-06
1.9
Performance data
Program blocks of the controller
The following number of program block types are available for control tasks:
RTU3030C: 42
RTU3031C: 43
In total, a maximum of 48 program blocks can be created in up to 8 networks. A maximum of
8 program blocks can be created per network.
For a description of the blocks, refer to the section Control functions (Page 24).
Configuration limits for program blocks
The number of configurable program blocks is limited for some types of blocks:
Program block
Max. number per block type
Total available
48
Pulse sequence
2
Year timer
8
Astronomical clock
4
Analog value processing
4
Statistics
8
Blocks with time functions use internal timer objects, which are also limited:
Program block
Number of timers used internally by a block instance
Total available
50
On-delay
1
Off delay
1
On/off delay
2
Retentive on delay
1
Pulse generator
2
Pulse sequence
1
Random on/off delay
2
Year timer
2
Week timer
2
Astronomical clock
2
Wiping relay
2
Time relay
3
Содержание Simatic RTU3030C
Страница 248: ...Configuration WBM 4 24 Tag tables RTU303xC 248 Operating Instructions 06 2019 C79000 G8976 C382 06 ...
Страница 350: ...Dimension drawings RTU303xC 350 Operating Instructions 06 2019 C79000 G8976 C382 06 Figure B 2 Side view ...
Страница 376: ...Accessories C 7 Overvoltage protection modules RTU303xC 376 Operating Instructions 06 2019 C79000 G8976 C382 06 ...
Страница 390: ...Documentation references E 10 10 RTU303xC 390 Operating Instructions 06 2019 C79000 G8976 C382 06 ...