Status IDs - DNP3
The status IDs correspond to the following elements of the specification:
OBJECT FLAGS - DNP3 Specification, Volume 6, Data Object Library-Part 1
Table 4- 9
DNP3: Bit assignment of the status byte for DNP3 data points
Bit
7
6
5
4
3
2
1
0
Flag name
-
-
-
LOCAL_
FORCED
DISCONTI
NUITY
OVER_
RANGE
RESTART ONLINE
Meaning
-
-
-
Local oper-
ator control
Counted
value over-
flow before
reading the
value
Value
range ex-
ceeded,
analog
value
Value not
updated
after start
Value is
invalid
Bit status
not sup-
ported
(always 0)
not sup-
ported
(always 0)
not sup-
ported
(always 0)
not sup-
ported
(always 0)
not sup-
ported
(always 0)
1
1
1
Status IDs - IEC
The status IDs correspond to the following elements of the specification:
Quality descriptor - IEC 60870 Part 5-101
Table 4- 10 IEC: Bit assignment of the status byte for IEC data points
Bit
7
6
5
4
3
2
1
0
Flag name
-
-
SB
substituted
-
CY
carry
OV
overflow
NT
not topical
IV
invalid
Meaning
-
-
Substitute
value
-
Counted
value-
overflow
before
reading the
value
Value -
range ex-
ceeded,
analog
value
Value not
updated
Value is
invalid
Bit status
not sup-
ported
(always 0)
not sup-
ported
(always 0)
not sup-
ported
(always 0)
not sup-
ported
(always 0)
not sup-
ported
(always 0)
1
1
0
4.23.8
Wake-up call / wake-up SMS
Waking the RTU from sleep mode
The RTU can be woken out of the sleep mode with a wake-up call from a mobile phone.
When using the communications protocol "TeleControl Basic", the RTU can also be woken
by a wake-up SMS message that can be generated by TCSB. For other communications
protocols the SINEMA Remote Connect server can also send a wake-up SMS message.
Содержание Simatic RTU3030C
Страница 248: ...Configuration WBM 4 24 Tag tables RTU303xC 248 Operating Instructions 06 2019 C79000 G8976 C382 06 ...
Страница 350: ...Dimension drawings RTU303xC 350 Operating Instructions 06 2019 C79000 G8976 C382 06 Figure B 2 Side view ...
Страница 376: ...Accessories C 7 Overvoltage protection modules RTU303xC 376 Operating Instructions 06 2019 C79000 G8976 C382 06 ...
Страница 390: ...Documentation references E 10 10 RTU303xC 390 Operating Instructions 06 2019 C79000 G8976 C382 06 ...